Customization: | Available |
---|---|
Output Type: | Single |
Warranty: | 2 Years |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
MODEL | DR-120-12 | DR-120-24 | DR-120-48 | |
DC VOLTAGE | 12V | 24 V | 48V | |
RATED CURRENT | 10A | 5A | 2.5A | |
CURRENT RANGE | 0-10A | 0-5A | 0-2.5A | |
RATED POWER | 120W | 120W | 120W | |
RIPPLE & NOISE (max.) Note.2 | 80mVp-p | 80mVp-p | 100mVp-p | |
OUTPUT | VOLTAGE ADJ. RANGE | 12- 14V | 24-28V | 48 - 53V |
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±1.0% | ±1.0% | |
LINE REGULATION | ±0.5% | ±0.5% | ±0.5% | |
LOAD REGULATION | ±1.0% | ±1.0% | ±1.0% | |
SETUP, RISE TIME | 500ms, 70ms/230VAC 500ms, 70ms/115VAC at full load | |||
HOLD UP TIME (Typ.) | 36ms/230VAC 32ms/115VAC at full load | |||
VOLTAGE RANGE | 88 -132VAC/176 - 264VAC by switch,248 - 370VDC | |||
FREQUENCY RANGE | 47~63Hz | |||
INPUT | EFFICIENCY (Typ.) | 80% | 84% | 85% |
AC CURRENT (Typ.) | 2.6A/115VAC 1.6A/230VAC | |||
INRUSH CURRENT (Typ.) | COLD START 20A/115VAC 40A/230VAC | |||
LEAKAGE CURRENT | <3.5mA/240VAC | |||
OVERLOAD | 105 -150% rated output power | |||
Protection type: Constant current limiting, recovers automatically after fault condition is removed | ||||
PROTECTION | OVERVOLTAGE | 15-16.5V | 29 - 33V | 58 -65V |
Protection type: Shut down o/p voltage, re-power on to recover | ||||
OVER TEMPERATURE | 85"C ±5"C (TSW1) | 90"C+5"C(TSW1) | 90'C ±5"C(TSW1) | |
Protection type: Shut down o/p voltage, recovers automatically after temperature goes down | ||||
WORKING TEMP. | -10 - +60"C (Refer to "Derating Curve") | |||
ENVIRONMENT | WORKING HUMIDITY | 20 - 90% RH non-condensing | ||
STORAGE TEMP., HUMIDITY | -20 - +85 "C, 10 - 95% RH | |||
TEMP. COEFFICIENT | ±0.03%/"C (0-50'C) | |||
VIBRATION | 10 - 500Hz, 2G 10min./1 cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 | |||
SAFETY STANDARDS | UL508, UL60950-1, TUV EN60950-1 approved | |||
SAFETY & | WITHSTAND VOLTAGE | l/P-0/P:3KVAC l/P-FG:1.5KVAC 0/P-FG:0.5KVAC | ||
EMC | ISOLATION RESISTANCE | l/P-O/P, l/P-FG, 0/P-FG:100M Ohms/500VDC/25,C/70% RH | ||
(Note 4) | EMC EMISSION | Compliance to EN55011 .EN55022 (CISPR22) Class B, EN61000-3-2.-3 | ||
EMC IMMUNITY | Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A | |||
MTBF | 432.1Khrs min. MIL-HDBK-217F (25'C) | |||
OTHERS | DIMENSION | 65.5*125.2*100mm (W*H*D) | ||
PACKING | 0.79Kg; 20pcs/16.5Kg/1.29CUFT | |||
1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25'C of ambient temperature. | ||||
2.Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1 uf & 47uf parallel capacitor. | ||||
3.Tolerance : includes set up tolerance, line regulation and load regulation. | ||||
4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. | ||||
NOTE |